| Caracteristici principale: |
- recomandat pentru incaperi umede (sere, bazine de inot etc.) iar vara pentru climatizare
- este universal deoarece incalzeste bine si cu ventilatorul oprit
- putere calorica mare
- cele mai cautate tipuri din categoria cu ventilator
|
| Intrebuintare: |
|
- Este cel mai universal ventiloconvector din tipurile pentru incaperi umede.
|
| Dimensiuni de gabarit: |
| Latime |
305 mm |
| Inaltime |
128 mm |
| Lungime |
900-3000 mm |
|
 |
|
|
| Capacitate calorica Q(W) |
|
Ventilator oprit
tA=20°C |
Ventilator treapta I
tA=20°C |
Ventilator treapta II
tA=20°C |
Ventilator treapta III
tA=20°C |
|
L=900 |
L=900 |
L=900 |
L=900 |
| Δt 60 |
298 |
1042 |
1135 |
1458 |
| Δt 50 |
223 |
830 |
904 |
1162 |
| Δt 30 |
90 |
401 |
437 |
561 |
|
L=1250 |
L=1250 |
L=1250 |
L=1250 |
| Δt 60 |
472 |
1650 |
1797 |
2309 |
| Δt 50 |
354 |
1315 |
1432 |
1841 |
| Δt 30 |
142 |
635 |
692 |
888 |
|
L=1500 |
L=1500 |
L=1500 |
L=1500 |
| Δt 60 |
597 |
2084 |
2270 |
2916 |
| Δt 50 |
447 |
1661 |
1808 |
2325 |
| Δt 30 |
180 |
803 |
874 |
1121 |
|
L=1750 |
L=1750 |
L=1750 |
L=1750 |
| Δt 60 |
721 |
2518 |
2742 |
3524 |
| Δt 50 |
540 |
2007 |
2185 |
2810 |
| Δt 30 |
217 |
970 |
1056 |
1355 |
|
L=2000 |
L=2000 |
L=2000 |
L=2000 |
| Δt 60 |
845 |
2952 |
3216 |
4131 |
| Δt 50 |
633 |
2352 |
2561 |
3293 |
| Δt 30 |
255 |
1137 |
1238 |
1589 |
|
L=2250 |
L=2250 |
L=2250 |
L=2250 |
| Δt 60 |
950 |
3321 |
3618 |
4648 |
| Δt 50 |
713 |
2646 |
2882 |
3705 |
| Δt 30 |
286 |
1280 |
1393 |
1787 |
|
L=2500 |
L=2500 |
L=2500 |
L=2500 |
| Δt 60 |
1094 |
3821 |
4161 |
5346 |
| Δt 50 |
819 |
3044 |
3315 |
4262 |
| Δt 30 |
329 |
1472 |
1602 |
2056 |
|
L=2750 |
L=2750 |
L=2750 |
L=2750 |
| Δt 60 |
1162 |
4059 |
4421 |
5681 |
| Δt 50 |
871 |
3235 |
3522 |
4528 |
| Δt 30 |
350 |
1564 |
1702 |
2184 |
|
L=3000 |
L=3000 |
L=3000 |
L=3000 |
| Δt 60 |
1342 |
4688 |
5107 |
6562 |
| Δt 50 |
1006 |
3736 |
4068 |
5231 |
| Δt 30 |
405 |
1807 |
1967 |
2523 |
Δt=tw1/tw2/tA ,Δt60=85/75/20°C, Δt50=75/65/20°C, Δt60=55/65/20°C, unde: L lungime convector, tA temperatura aerului, tw1 temperatura apei la intrare, tw2 temperatura apei la iesire1
Alte valori pt Δt se calculeaza cu formula conform SR EN 442:
Q=KMΔtn ecuatia caracteristica unde KM=6,8617 constanta modelului n=1,3529 |
|
|